Relay output wiring, Ca-6075 class a expander installation – Potter PFC-6030 User Manual
Page 30

3-24
PFC-6030 • 5403595 • Rev C • 2/13
Relay Output Wiring
The panel has three (3) dedicated common relays. The dedicated trouble relay is a fail safe trouble relay that changes position
anytime a trouble condition occurs.
Relays have a contact rating of 24vDC / 3.0A, 125vAC / 3A, and Power Factor of 1.0. These outputs are non-power limited and
not supervised.
Note: If the power supply connected to the devices is power-limited, then the outputs are power limited.
Relay Outputs
Figure 25.
TROUBLE
NC COM NO
SUPERVISORY
NC COM NO
ALARM
NC COM NO
CA-6075 Class A Expander Installation
The Class A configuration requires the use of the CA-6075. Once the card is installed, the additional terminals are provided for
the return loop of the NAC. The CA-6075 provides the terminals for both NACs, SLCs, and P-Link. Refer to the figures below for
examples of installing and wiring a Class A expander card.
Notes:
One (1) CA-6075 Class A expander may be installed per panel.
1.
The CA-6075 provides the terminals for NACs, P-Link, and SLCs.
2.
Examples of Installing and Wiring a Class A Expander Card
Figure 26.
CA-6075
Class A Expander
#6-32 x 7/8 screws
5050793 bracket
#6-32 x 1/4 screws
guide pins
DWG #593-27
NAC 1 NAC 2
-
+ -
+
Notification
Appliance
NAC 1 NAC 2
-
+ -
+
DWG #602-5A
CA-6075 Class A card
DWG #593-26