beautypg.com

Appendix f: troubleshooting tips – Potter PFC-6030 User Manual

Page 120

background image

F-1

PFC-6030 • 5403595 • Rev C • 2/13

Appendix F: Troubleshooting Tips

This section provides basic error messages, their descriptions and recommended actions for each condition.

Troubleshooting

Table 26:

Error Message

Error Description/Action

Keypad “##”: Missing

The panel is not able to communicate with the annunciator.

Action: Check wiring and programming.

SLC “##”: TYPe eRR

Device is not programmed for the correct function.

Action: Program device for correct function.

SLC “##”: XTRA Dev

FACP found a non-programmed device.

Action: Run LEARN or program specific device.

SLC “##”: DUP ADDR

FACP found multiple devices with the same address.

Action: Manually reassign address of one of the devices.

SLC LOOP SHORTeD

There is a short on the SLC loop wiring.

Action: Locate short and repair accordingly.

NAC “##”: OPeN

There is an open on the wiring.

Action: Locate open and repair accordingly.

NAC “##”: Shorted

There is a short on the Notification Circuit’s wiring.

Action: Locate short and repair accordingly.

SLC 1: Missing

The panel is not able to communicate with a device.

Action: Check device is currently operating and/or connect device to SLC loop.

SLC “##”: OPeN/PWR

Monitored Output Module is missing 24 vDC connection.

•y

Action: Check for 24 VDC to the device.

Back up batteries are missing or need to be replaced.

•y

Action: Connect or replace batteries as needed.