Potter PFC-6030 User Manual
Page 82

5-76
PFC-6030 • 5403595 • Rev C • 2/13
NAC Functions
The two (2) on-board circuits (NACs 1&2) are automatically configured as “General Purpose”, but may be reconfigured and
renamed. Refer to the table below for descriptions of the configuration functions.
NAC Circuit Configuration Functions
Table 18:
Function
Description
Unused
Circuit is unused.
General Purpose
General purpose NAC; obeys zone “output pattern” programming.
Potter Sync
Drives Potter synchronized horns / strobes.
Gentex Sync
Drives Gentex synchronized horns / strobes.
System Sensor Sync
Drives System Sensor synchronized horns / strobes.
Wheelock Sync
Drives Wheelock synchronized horns / strobes.
Aux Constant
Constant DC power.
Aux Resettable
Constant DC power; disconnects power during system reset.
Aux Door Holder
Constant DC power; disconnects when an alarm occurs.
Aux Door Holder Low AC Drop
Constant DC power; disconnects on AC Loss or when an alarm occurs.
Aux ANSI
Always on ANSI pattern used for ASB pattern synchronization.
City Tie
Municipal box connection