beautypg.com

10 air filter replacement – AERCO Innovation (G-14-2265 and above) User Manual

Page 91

background image

Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 6 – MAINTENANCE

OMM-0078_0L

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 91 of

206

GF-128

Phone: 800-526-0288

PRI: 11/25/2014

Figure 6-10. External Condensate Trap– Cross-Sections

6.10 AIR FILTER REPLACEMENT

The Innovation heater is equipped with an air filter (part no. 59138) which should be cleaned or
replaced every 12 months. The air filter is located at the inlet of the air fuel valve as shown in
Figure 6-11.

To inspect/replace the air filter, proceed as follows:

Air Filter Replacement

1.

Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power
from the unit

2.

Remove the side panels from the unit.

3.

Refer to Figure 6-11 and locate the air filter attached to the air/fuel valve inlet.

4.

Using a flat-tip screwdriver or 5/16” nut driver, loosen the clamp securing the filter to the
inlet flange of the air/fuel valve. Remove the filter and clamp.

5.

Each replacement air filter is equipped with its own clamp. Therefore, simply install the
replacement air filter on inlet flange of the air fuel valve and tighten the clamp with a flat-tip
screwdriver or 5/16” nut driver.

6.

Replace the side panels on the unit and return heater to service use.


THUMB

SCREWS

(4)

CONDENSATE TRAP
COVER O-RING

FLOAT

THUMB

SCREW

O-RINGS

(2)

ADAPTOR

OPENING

3/4" NPT Port

3/4" NPT PORT

OUTLET