beautypg.com

9 rs485 comm terminals, 10 rs232 comm terminals, 11 vfd/blower terminals – AERCO Innovation (G-14-2265 and above) User Manual

Page 32: 12 interlock terminals, 1 remote intl’k terminals, 2 delayed intl’k terminals

background image

Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 2 – INSTALLATION

Page 32 of

206

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0L

PRI: 11/25/2014

Phone: 800-526-0288

GF-128

3. When the 4-20mA is selected for the Analog Output, the 0-10VDC is disabled at the

VFD/Blower terminals, and the selected output is available at the terminals labeled
Analog Output +/-.

2.12.9 RS485 Comm Terminals

The RS485 communication terminals (+, GND, & -) are used when the Innovation Water
Heaters are being controlled by an Energy Management System (EMS) or the C-More Water
Heater Management (WHM) system using Modbus (RS485) communication. The WHM
software required to control up to 8 AERCO Innovation Water Heaters is included in the C-More
Control System used with each Innovation unit.

2.12.10 RS232 Comm Terminals

As of Firmware version 4.0 and above, these terminals are used only by factory-trained
personnel to monitor OnAER communications via a portable computer.

2.12.11 VFD/BLOWER Terminals

These terminals (0-10 & AGND) send an analog signal to control the blower speed. When any
of the 4-20mA options is selected for the Analog Outputs (Section 2.12.8), the output from the
VFD/Blower terminals is disabled.

2.12.12 Interlock Terminals

The unit offers two interlock circuits for interfacing with Energy Management Systems and
auxiliary equipment such as pumps or louvers or other accessories. These interlocks are called
the Remote Interlock and Delayed Interlock (REMOTE INTL’K IN and DELAYED INTL’K IN in
Figure 2-12). Both interlocks, described below, are factory wired in the closed position.

NOTE

Both the Remote Interlock and Delayed Interlock must be in the closed
position for the unit to fire.

2.12.12.1

REMOTE INTL’K Terminals

The remote interlock circuit is provided to remotely start (enable) and stop (disable) the unit if
desired. The circuit is 24 VAC and comes factory pre-wired closed (jumped).

2.12.12.2

DELAYED INTL’K Terminals

The delayed interlock is typically used in

conjunction

with the Auxiliary Relay Contacts

described in section 2.12.14. This interlock circuit is located in the purge section of the start
string. It can be connected to the proving device (end switch, flow switch etc.) of an auxiliary
piece of equipment started by the unit’s auxiliary relay. The delayed interlock must be closed for
the heater to fire. If the delayed interlock is connected to a proving device that requires time to
close (make), a time delay (Aux Start On Dly) that holds the start sequence of the unit long
enough for a proving switch to make (close) can be programmed.

Should the proving switch not prove within the programmed time frame, the unit will shut down.
The Aux Start On Dly can be programmed from 0 to 120 seconds. This option is located in the
Configuration Menu (Chapter 3).