Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

OMM-0078_0L

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 45 of

206

GF-128

Phone: 800-526-0288

PRI: 11/25/2014

Table 3-4. Configuration Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

1

Internal Setpt

Lo Temp Limit

Hi Temp Limit

130°F

2

Unit Type

Innovation WH

Innovation WH

3

Unit Size

600 MBH, 800 MBH, 1060 MBH,

1350 MBH

600, 800, 1060 or

1350 MBH

4

Fuel Type

Natural Gas, Propane

Natural Gas

5

Water Heater Mode

Constant Setpoint,

Remote Setpoint,

Constant Setpoint

6

Remote Signal
(If Mode = Remote Setpoint,
Direct Drive or Combination)

4 – 20 mA/1 – 5V

0 -20 mA/0 – 5V

PWM Input (Legacy BMS),

Network

4 – 20 mA,

1-5V

7

Outdoor Sensor

Enabled or Disabled

Disabled

8

System Start Tmp
(If Outdoor Sensor =Enabled)

30°F

100°F

60°F

9

Setpt Lo Limit

40°F

Setpt Hi Limit

60°F

10

Setpt Hi Limit

Setpt Lo Limit

190°F

150°F

11

Temp Hi Limit

40°F

200°F

160°F

12

Max Valve Position

40%

100%

100%

13

Pump Delay Timer

0 min.

30 min.

0 min.

14

Aux Start On Dly

0 sec.

120 sec.

0 sec.

15

Failsafe Mode

Shutdown or Constant Setpt

Shutdown

16

* Analog Output

Off, Setpoint, Outlet Temp, Valve Pos

4-20mA, valve Pos 0-10v

Valve Pos 0-10v

17

Low Fire Timer

2 sec.

600 sec.

2 sec.

18

Setpt Limiting

Enabled or Disabled

Disabled

19

Setpt Limit Band

0°F

10°F

0

20

Network Timeout

5 Sec

999 Sec

30 Sec

21

Shutoff Dly Temp

0

25

8

22

Demand Offset

0

25

5

23

Deadband High

0

25

0

24

Deadband Low

0

25

0