CHAPTER 8 – WATER HEATER MANAGEMENT

OMM-0078_0L

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 121 of

206

GF-128

Phone: 800-526-0288

PRI: 11/25/2014

WHM MENU

See section 8-6 for a range of choices and the default values.

ITEM

MENU LEVEL &

OPTION

DESCRIPTION

13

WHM Min Addr

Set the minimum address of the heaters to be controlled by the
master. The WHM Min Addr and WHM Max Addr must differ by no
more than 7.

14

WHM Max Addr

Set the maximum address of the heaters to be controlled by the
master. The WHM Min Addr and WHM Max Addr must differ by no
more than 7.

15

SSD Address

The Modbus Address of the SSD Device (Protonode). Set this
address to 247 if the WHM system is being monitored by a Protonode
with Slave –Slave (SSD) programming. Set to zero (0) if no Protonode
is installed.

16

SSD Temp Format

SSD temp values can be accessed in Degrees or Points

17

1 Valve Status 8

Displays the valve status of all the units.

0= valve closed

1= valve open

2= valve stuck closed

3= valve stuck open

18

1 Comm Errors 8

Display Comm Errors of all the units.

19

20

WHM On Delay

WHM off Delay

Specifies the WHM On and Off time delays associated with the Next
ON VP and Next OFF VP menu options. Therefore, if the Next ON VP
or Next OFF VP is at its preset Valve Position (%) for the specified
Delay period, another heater will be turned ON or OFF. This is done
to prevent cycling units on and off during short changes in load.

21

Over WHM Under

This value is a Factory debugging tool.

22

WHM Min Units

Specifies the Minimum number of units required to be “on” or “active”.

23

WHM Warmup Time

Specifies the time a valve will remain closed when turning on a unit in
order to assure that we do not release cold water into the building.
When turning on a unit, the valve will open when either the Warmup
Timer times out or the FeedForward Temperature reaches Setpoint.

24

WHM On Timeout

Specifies the time the WHM Master waits for a slave unit to turn On.

25

WHM Valve State

Displays the status of the WHM Sequencing Valve.

(1 = ON, 0 = OFF)