Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 2 – INSTALLATION

Page 18 of

206

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0L

PRI: 11/25/2014

Phone: 800-526-0288

GF-128

2.4 SITE PREPARATION

Ensure that the site selected for installation of the Innovation Water Heater includes:

• Access to AC Input Power at 120 VAC, Single-Phase, 60 Hz @ 20 Amps.
• Access to Natural Gas line at a minimum pressure of 4 inches W.C. or to Propane at a

minimum pressure of 7 inches W.C. with the unit operating at maximum capacity.

2.4.1 Installation Clearances

All Innovation Models are packaged in enclosures having identical exterior dimensions. The unit
must be installed with the prescribed clearances for service as shown in Figure 2-1 (shown with
optional Sequencing Valve). The minimum clearance dimensions, required by AERCO, are
listed below. However, if Local Building Codes require additional clearances, these codes shall
supersede AERCO’s requirements. Minimum acceptable clearances required are as follows:

Sides: 24 inches

Front: 24 inches

Rear:

30 inches

Top:

18 inches

All gas piping, water piping and electrical conduit or cable must be arranged so that they do not
interfere with the removal of any panels, or inhibit service or maintenance of the unit.

50.9"

18"

97.25"

75.25"

18.6"

SEQUENCING

VALVE

30"

24"

24"

24"

4" HIGH PAD

Figure 2-1. Innovation Water Heater Clearances

KEEP THE UNIT AREA CLEAR AND FREE FROM ALL COMBUSTIBLE
MATERIALS AND FLAMMABLE VAPORS OR LIQUIDS

.

While packaged in the shipping container, the unit must be moved by pallet
jack or forklift from the FRONT ONLY.

WARNING

CAUTION

Ensure that the housekeeping pad does NOT extend
under the condensate assembly.