APPENDIX J – COMBUSTION CALIBRATION (KOREA ONLY)

The Innovation Heater is combustion calibrated at the factory prior to shipping. However,
recalibration as part of initial start-up is necessary due to changes in the local altitude, gas BTU
content, gas supply piping and supply regulators. Factory Test Data sheets are shipped with
each unit. These sheets must be filled out and returned to AERCO for proper Warranty
Validation.

It is important to perform the following procedure as outlined below. This will keep
readjustments to a minimum and provide optimum performance.

Natural Gas Combustion Calibration

1. Open the water supply and return valves to the unit and ensure that the system pumps

are running.

2. Open the natural gas supply valve(s) to the unit.

3. Set the control panel ON/OFF switch to the OFF position.

4. Turn on external AC power to the unit. The display will show LOSS OF POWER and the

time and date.

5. Set the unit to the Manual Mode by pressing the AUTO/MAN key. A flashing Manual

Valve Position message will be displayed with the present position in %. Also, the
MANUAL LED will light.

6. Adjust the air/fuel valve position to 0%

by pressing the ▼ arrow key.

7. Ensure that the leak detection ball valve downstream of the SSOV is open.

8. Set the ON/OFF switch to the ON position.

9. Change the valve position to 29%

using the ▲ arrow key. The unit should begin its start

sequence and fire.

10. Next, verify that the gas pressure downstream of the SSOV is within the appropriate range

shown below for the Innovation Model being tested. If gas pressure adjustment is
required, remove the brass hex nut on the SSOV actuator to access the gas pressure
adjustment screw (Figure J-1). Make gas pressure adjustments using a flat-tip screwdriver
to obtain a gas pressure reading within the required range for the INN model being tested.


INNOVATION
MODEL

GAS PRESSURE RANGE

DOWNSTREAM OF SSOV

INN1350

2.8” – 3.0” W.C.

INN1060

2.4” – 2.6” W.C.

INN800

1.3” – 1.5” W.C.

INN600

0.7” – 0.9” W.C.