7.2 ADDITIONAL FAULTS WITHOUT SPECIFIC FAULT MESSAGES

Refer to Table 7-2 to troubleshoot faults which may occur without a specific fault message being displayed.

TABLE 7-2. WATER HEATER TROUBLESHOOTING WITH NO FAULT MESSAGE DISPLAYED

OBSERVED INCIDENT

PROBABLE CAUSES

CORRECTIVE ACTION

Fluctuating Gas Pressure

1.

Gas pressure going into unit is
fluctuating.

2.

Damping Orifice not installed.

1.

Stabilize gas pressure going into unit. If necessary,
troubleshoot Building Supply Regulator.

2.

Check to ensure that the Damping Orifice is installed in the
SSOV Actuator shown in Figure 7-3. (For DBB Gas Trains,
the Damping Orifice is installed in the downstream SSOV
Actuator).

Air/Fuel Valve “hunting” at

the 80% Valve Position

1.

IGST and Power Supply Boards
in Control Box are outdated.

1.

Check to ensure that the IGST and Power Supply Boards
are Rev. E or higher.