CHAPTER 8 – WATER HEATER MANAGEMENT

OMM-0078_0L

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 117 of

206

GF-128

Phone: 800-526-0288

PRI: 11/25/2014

Example:
If a Master is enabled and in Standby mode, the C-More display will show as follows:



8.5 BST ALTERNATING STATUS DISPLAYS

Master/Slave Status Displays:

On both WHMS Master and Slave heaters, the following status information will alternate, and be
displayed on the two line VFD display on the front of the C-More.

FAILSAFE ACTIVE

The Slave Failsafe Mode has been activated

All Heaters On

All available heaters are ignited

All Heaters Off

All available heaters are off

Enabling First

The first heater is allowed to ignite and its valve is opened

Enabling Next

The next heater is allowed to ignite and it’s valve is opened

Wtr Htr Inactive

This Slave unit is inactive, its valve is closed and can’t ignite

Wtr Heatr Active

This Slave unit is active, its valve is opened and it can ignite

REMOTE SIG FAULT Remote signal fault
WHMS FAILSAFE

WHMS is in Failsafe Mode


Example: If all available heaters are turned off, the C-More display will alternate the display
above (MASTER-STANDBY) with the All Heaters Off status message as follows:





8.6 WHM MENU

The WHM Menu in each C-More can only be viewed when the Unit Type option in the
Configuration Menu is set to Innovation WH. Most of the options in this menu are preset at the
factory and cannot be altered by the user.

A full description of each item appears in section 8.7 – WHM Menu Item Descriptions.

NOTES

Some of the WHM menu items appear only if they are enabled, either in
the WHM Menu or by a specific menu item. For example, item 31, WHM
Header Temp, does not appear unless item 30, MB Head Temp En =
Enable.

In addition to the WHM Menu items listed in Table 8-1, the Setup Menu
contains a Comm Address option which must be entered for each unit to
enable WHM control of the system.