Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 5 – SAFETY DEVICE TESTING

Page 76 of

206

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0L

PRI: 11/25/2014

Phone: 800-526-0288

GF-128

Ignition Switch Open During Ignition – Continued

5.

Initiate a unit start sequence.

6.

The unit should begin its start sequence and then shut down and display IGN SWITCH
OPEN DURING IGNITION
.

7.

Replace the wire on the Ignition Switch and press the CLEAR button. The unit should
restart.

Figure 5-7. Typical Air/Fuel Valve Cover Location

Figure 5-8. Air/Fuel Valve Purge and Ignition Switch Locations

5.12 SAFETY PRESSURE RELIEF VALVE TEST

Test the safety Pressure Relief Valve in accordance with ASME Pressure Vessel Code, Section
VI.

AIR/FUEL VALVE

COVER

(Rotate CCW to

Ignition

Position

Purge

Position

Switch

TO BLOWER

VALVE
POSITION

170

169

172

171

AIR/FUEL VALVE
SWITCH WIRING

BREAKOUT

AIR IN