beautypg.com

AERCO Innovation (G-14-2265 and above) User Manual

Page 48

background image

Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

Page 48 of

206

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0L

PRI: 11/25/2014

Phone: 800-526-0288

GF-128

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

9

Exhaust Tmp Dsp

Enabled or Disabled

10

VP Up Rate

0.5

60.0

Depends on unit type/size

11

VP Down Rate

0.5

60.0

Depends on unit type/size

12

Purge Blwr Offst

-1.0

8.0

Depends on unit type/size

13

4-20mA Purge Pct

60%

100%

70%

14

PWM In Adj

-5.0%

5.0%

0.0%

15

Analog In Adj

-5.0%

5.0%

0.0%

16

Flow In Adj

-5.0%

5.0%

0.0%

17

Supply Gas Pressure In Adj

-5.0%

5.0%

0.0%

18

Gas Plate dp In Adj

-5.0%

5.0%

0.0%

19

mA Out Adj

-1.0 mA

1.0 mA

0.0 mA

20

A/F Sensitivity

1%

5%

2%

21

Power Reset

Automatic or Manual

Automatic

22

Water Temp Reset

Automatic or Manual

Automatic

23

Gas Press Reset

Automatic or Manual

Manual

24

Min Off Time

0 Min

15 Min

0 Min

25

Heatr Tuning Dsp

Enabled or Disabled

Disabled

26

Heatr Bkpt Dsp

Enabled or Disabled

Disabled

27

Stop Level

0%

Start Level

16

28

Start Level

Stop Level

40%

20

29

Skip Range Cntr

10

95

40

30

Skip Range Span

0

3

0

31

Skip Speed

5

20

5

32

O2 Gain

920

1126

1024

33

O2 Offset

-3.0

+3.0

0

34

O2 Sensor

Enabled or Disabled

Depends on unit type/size

35

Cal Temp Sensors

Enabled or Disabled

36

FFWD Temp Offset

-20

+20

0

37

Exhst Tmp Offset

-20

+20

0

38

Outdr Air Offset

-20

+20

0

39

Inlet Air Offset

-20

+20

0

40

Inlet Wtr Offset

-20

+20

0

41

Outlet Wtr Offset

-20

+20

0

42

Spark Monitor

Enabled or Disabled

Depends on unit type/size

43

Min Spark Amps

0 Amps

2.5 Amps

0.1 Amps

44

Max Spark Amps

0 Amps

2.5 Amps

0.4 Amps