Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

OMM-0078_0L

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 47 of

206

GF-128

Phone: 800-526-0288

PRI: 11/25/2014

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

WHM Items – the following item appear only if WHM is enabled

20 FDback Start Pos

0%

100%

30%

21 Fdback End Pos

0%

100%

60%

22 Max Feedback

0%

100%

30%

23 Fdback Value

0%

100%

Read Only Value

24 Temp Gov

Enable or Disable

Enable

25 GOV Limit-5

0

100

30

26 GOV Limit-7

0

100

20

27 GOV Limit-10

0

100

15

28 GOV Limit-12

0

100

10

29 GOV Limit-15

0

100

5

30 PID Output

0%

100%

Read Only Value

31 P Output

0%

100%

Read Only Value

32 I Output

0%

100%

Read Only Value

33 D Output

0%

100%

Read Only Value

34 Reset Defaults

Yes

No

No

3.8 CALIBRATION MENU

The Calibration Menu is used by Factory Trained Service personnel to adjust or reset the
parameters listed below.

A full description of each item appears in Table A-5 of Appendix A – Innovation Menu Item
Descriptions.

Table 3-6: Calibration Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

1

Stepper Fbk

Cal 0%

Cal 100%

Verify 50%

Cal 0%

2

Purge Timer

5 sec.

60 sec

Depends on unit type/size

3

Post Purge Timer

0 sec.

60 sec.

0 sec.

4

IGN Position

5%

60%

Depends on unit type/size

5

FFWD Temp Disply

Enabled or Disabled

6

Outlet Tmp Dsply

Enabled or Disabled

7

Inlet Tmp Dsply

Enabled or Disabled

8

Valv Pos Out Dsp

Enabled or Disabled