8 calibration menu – AERCO Innovation (G-14-2265 and above) User Manual
Page 47
Innovation Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0078_0L
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 47 of
206
GF-128
Phone: 800-526-0288
PRI: 11/25/2014
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
WHM Items – the following item appear only if WHM is enabled
20 FDback Start Pos
0%
100%
30%
21 Fdback End Pos
0%
100%
60%
22 Max Feedback
0%
100%
30%
23 Fdback Value
0%
100%
Read Only Value
24 Temp Gov
Enable or Disable
Enable
25 GOV Limit-5
0
100
30
26 GOV Limit-7
0
100
20
27 GOV Limit-10
0
100
15
28 GOV Limit-12
0
100
10
29 GOV Limit-15
0
100
5
30 PID Output
0%
100%
Read Only Value
31 P Output
0%
100%
Read Only Value
32 I Output
0%
100%
Read Only Value
33 D Output
0%
100%
Read Only Value
34 Reset Defaults
Yes
No
No
3.8 CALIBRATION MENU
The Calibration Menu is used by Factory Trained Service personnel to adjust or reset the
parameters listed below.
A full description of each item appears in Table A-5 of Appendix A – Innovation Menu Item
Descriptions.
Table 3-6: Calibration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
1
Stepper Fbk
Cal 0%
Cal 100%
Verify 50%
Cal 0%
2
Purge Timer
5 sec.
60 sec
Depends on unit type/size
3
Post Purge Timer
0 sec.
60 sec.
0 sec.
4
IGN Position
5%
60%
Depends on unit type/size
5
FFWD Temp Disply
Enabled or Disabled
6
Outlet Tmp Dsply
Enabled or Disabled
7
Inlet Tmp Dsply
Enabled or Disabled
8
Valv Pos Out Dsp
Enabled or Disabled