beautypg.com

7 over-temperature limit switches – AERCO Innovation (G-14-2265 and above) User Manual

Page 65

background image

Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 4 – INITIAL START-UP

OMM-0078_0L

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 65 of

206

GF-128

Phone: 800-526-0288

PRI: 11/25/2014

4.7 OVER-TEMPERATURE LIMIT SWITCHES

The unit contains both automatic and manual reset over-temperature limit switches, shown in
Figure 4-6. They can be accessed by opening the front panel door of the unit.

The manual reset switch is not adjustable and is permanently fixed at 190°F. This switch will shut
down and lock out the heater if the water temperature exceeds 190°F. Following an over-
temperature condition, it must be manually reset by pressing the RESET button before the heater
can be restarted. The automatic reset over-temperature switch is adjustable and allows the unit to
restart, once the temperature drops below its temperature setting. Set the automatic over-
temperature switch to the desired setting.

Figure 4-6. Over-Temperature Limit Switch Location

MANUAL RESET (NON-
ADJUSTABLE)
OVER-
TEMPERATURE LIMIT
SWITCH

AUTOMATIC RESET

(ADJUSTABLE) OVER-

TEMPERATURE LIMIT

SWITCH