Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 8 – WATER HEATER MANAGEMENT

OMM-0078_0L

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 119 of

206

GF-128

Phone: 800-526-0288

PRI: 11/25/2014

SN

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

32. Mdbus Temp Units

˚F or ˚C

˚F

33. Header Temp Addr

0

255

240

34. Header Tmp Point

0

255

14

35. MB Outdr Sens En

Enable or Disable

Disable

36. WHM Outdr Temp

0

0

Outdr Temp

37. Outdoor Tmp Addr

0

255

240

38. Outdoor Tmp Pnt

0

255

15

39. Err Threshold

1

9

5

40. Comm Address

0

127

0

41.

1 WHM Units 8
(for 1 – 8 units)

Displays the following character for each unit
(Default = 0):

0 = Off
1 = On
- = Off-Line
* = Not available (fault, etc.)
A = Lead On
B = Lag On
a = Lead Off

b = Lag Off

* NOTE

The Level 2 Password (6817) in the Setup Menu must be entered
to view or change the WHM Auto Mstr and WHM Auto Timer
options (items 11 and 12, above).

8.7 WHM MENU ITEM DESCRIPTIONS

The required settings for WHM Menu items will vary depending on the number of units
connected to the Modbus network and required setpoint and operating conditions to be
maintained on the network. Set the menu options in accordance with the descriptions provided
in Table 8-2, below.

NOTE

It is recommended that the WHM Menu settings described in the following
sections be performed first at the WHM Master. This will simplify the
number of required entries since most of the settings will be “pushed” to the
appropriate Slaves.