Innovation Water Heaters Installation, Operation & Maintenance Manual

APPENDIX A – INNOVATION MENU ITEM DESCRIPTIONS

OMM-0078_0L

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 135 of

206

GF-128

Phone: 800-526-0288

PRI: 11/25/2014

Table A-3: Configuration Menu Item Descriptions

Table A-3: CONFIGURATION MENU ITEM DESCRIPTIONS

See section 3-6 for a range of choices and the default values.

MENU LEVEL & OPTION

DESCRIPTION

1

Internal Setpoint

Allows internal setpoint to be set.

2

Unit Type

INNOVATION Water Heater

3

Unit Size

600 MBH, 800 MBH, 1060 MBH or 1350 MBH

4

Fuel Type

Allows selection of Natural Gas or Propane.

5

Heater Mode

It allows selection of: Constant Setpoint, or Remote Setpoint.

6

Remote Signal

Used to set the type of external signal which will be used
when operating in the Remote Setpoint Mode.

7

Outdoor Sensor

Allows outdoor sensor function to be enabled or disabled.

8

System Start Tmp

In Outdoor Reset mode, the temperature above which the
unit shuts down.

9

Setpoint Lo Limit

Used to set the minimum allowable setpoint (40°F to Setpoint
Hi Limit).

10

Setpoint Hi Limit

Used to set the maximum allowable setpoint (Setpoint Lo
Limit to 190°F).

11

Temp Hi Limit

This is the maximum allowable outlet temperature (40 to
200°F). Any temperature above this setting will turn off the
unit. The temperature must then drop 5°F below this setting
to allow the unit to run.

12

Max Valve Position

Sets the maximum allowable valve position for the unit (40%
to 100%).

13

Pump Delay Timer

Specifies the amount of time (0 to 30 min.) to keep the pump
running after the unit turns off.

14

Aux Start On Dly

Specifies the amount of time to wait (0 to 120 sec.) between
activating the Aux Relay (due to a demand) and checking the
pre-purge string to start the heater.

15

Failsafe Mode

Allows the Failsafe mode to be set to either Constant
Setpoint or Shutdown.

16

Analog Output

Must be set to Valve Pos 0-10V.

17

Lo Fire Timer

Specifies how long (2 to 600 sec.) to remain in the low fire
position after ignition, before going to the desired output

18

Setpt Limiting

N/A for Water Heaters

19

Setpt Limit Band

N/A for Water Heaters