Innovation Water Heaters Installation, Operation & Maintenance Manual

APPENDIX J – COMBUSTION CALIBRATION (KOREA ONLY)

OMM-0078_0L

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 201 of

206

GF-128

Phone: 800-526-0288

PRI: 11/25/2014

Natural Gas Combustion Calibration – Continued

15. Once the oxygen level is within the required range listed in step 13, the gas pressure on

the downstream side of the SSOV should be within the appropriate range shown below for
the Innovation Model being tested.


INNOVATION
MODEL

GAS PRESSURE RANGE
DOWNSTREAM OF SSOV

INN1350

2.8” – 3.0” W.C.

INN1060

2.4” – 2.6” W.C.

INN800

1.3” – 1.5” W.C.

INN600

0.7” – 0.9” W.C.

16. Replace the brass cap on the SSOV gas pressure adjustment if it was previously

removed.

17. This completes the combustion calibration procedure.