Analog output scaling (fs-n11mn only), Analog output scaling (fs-n11mn only) -21 – KEYENCE FS-N10 Series User Manual
Page 67
4-3 Detection Settings (Func)
4
Set
tings
f
o
r
Ad
v
an
ced F
u
nct
ion
s
4-21
- Digital Fiber Sensor FS-N10 Series User's Manual -
The FS-N11MN is equipped with the analog voltage output function.
In the initial setting, voltage is output within the range of 1-5 V to the displayed
received light intensity of 0 to 4000.
The received light intensity corresponding to analog voltage of 5V can be changed
within the range stated below:
Setting range of received light intensity corresponding to 5V:
50
to
65535
* (Initial value:
4000
)
Setting range of received light intensity corresponding to 1V:
0
fixed (cannot be changed)
0
* The FS-N11MN shipped before March 10, 2011 becomes 100 - 9999.
• Received light intensity corrected with the preset function and
DATUM1/2 mode is not reflected in the analog output.
• When the work preset function, maximum sensitivity preset func-
tion or full automatic preset function is used, correction is made
so that the light intensity that becomes "
.0
" will correspond to the
analog voltage of 1V.
• While various preset functions are enabled, pressing the [PRESET]
button on the Analog Scaling Setting screen automatically sets
analog output scaling values so that 5V will be output to the cur-
rent value of "
100.0
".
• When the analog scaling mode setting is changed, the analog out-
put scaling values will be automatically set each time preset is per-
formed. (Correction by presetting is reflected in the analog output.)
"Analog output scaling (FS-N11MN only)" (page 4-21)
• Correction of the received light intensity using the zero shift
function is reflected in the analog output.
Analog output scaling (FS-N11MN only)
Refer to page 4-2 "Detection Settings (Func)" for setting methods.
50
1V
5V
Output voltage
4000 (Initial value)
65535
Received light intensity
Point