beautypg.com

Motion sensor range, Network cable preparation, Cable details – KMC Controls KMD-1281 User Manual

Page 5

background image

NetSensor Installation and Operation

Revision A

5

Motion sensor range

33 feet (10 meters)

Network cable preparation

Connecting a NetSensor to a controller requires a six-wire cable with
RJ-12 connectors on each end. KMC plenum-rated preassembled
cables are recommended. Cables made to length must meet the
following requirements:

Cable length must be no longer than 75 feet (22.9 meters).

Cable conductors must be no smaller than #24 AWG.

Cable insulation must meet local building codes.

Connectors must be appropriate for the cable in use and are
installed following the connector manufacturers instructions.

Cable details

55°

10 m

32.8 ft

10 m

32.8 ft

X

10 m

32.8 ft

10 m

32.8 ft

46.5°

Y

Top view

Side view

RJ-12

This manual is related to the following products: