Applications, Fcu (fan coil unit)—2 pipe, modulating, Fcu (fan coil unit)—2 pipe, modulating 5 – KMC Controls BAC-14xx36 Series FlexStat User Manual
Page 5

BAC-12xx36/13xx36/14xx36 Series FlexStat
5
Installation Guide, Rev. C
Applications
FCU 2-PIPE MODULATING LAYOUT
CSE-1102
Air Differential Pressure Switch
VEP-45/
VEB-43
Valves
with
MEP-4002
0–10 VDC
Actuators
STE-1402
Duct Temp. Sensor, Type III
XEE-6311-050 Transformer
STE-1454
Strap-On Temp. Sensor, Type III
REE-3211 or CVR11C-0/LD96200 Multi-Voltage Relays
FCU (Fan Coil Unit)—2 Pipe, Modulating
Output
Terminals
FCU Output
Connections
BACnet
Objects
Analog 9
AO9
GND
Ground (for
analog output
terminals 7–9)
Analog 8
AO8
Analog 7
Valve (VLV)
AO7
Analog 6
AO6
GND
Analog 5
AO5
Analog 4
AO4
Relay 3
Fan 3
BO3
SC 1–3
24 VAC (for relay
terminals 1–3)
Relay 2
Fan 2
BO2
Relay 1
Fan 1
BO1
APPLICATION
DEGREES SCALE: °F
APP:
OPT: 2–PIPE
ADDITIONAL SETUP
FAN COIL
ADDITIONAL SETUP
FAN
OPTIMUM START
SENSORS
VALVE
NOTE: Do not use REE-3211/
CVR11C-0/LD96200
relay
s with analog
outputs! See Output
Connections on page 3.
Input Terminals
FCU Input Connections
BACnet Objects
IN9
Opt. Remote CO
2
Sensor*
AI9
IN8
AI8
IN7
Opt. Remote Temp. Sensor*
AI7
IN4
AI4
IN3
Supply Water Temp. (W-TMP)**
AI3
GND
Ground
IN2
Optional FST or DAT*
AI2
*Fan Status (FST), Discharge Air Temperature (DAT), and (not shown
on the diagram) remote temp./CO
2
sensors are optional inputs. Set
pull-up resistor switch positions appropriately (see the Input
Connections section).
**Input for Supply Water Temp is typically a 10K,Type III thermistor.