BAC-12xx36/13xx36/14xx36 Series FlexStat

5

Installation Guide, Rev. C

Applications

FCU 2-PIPE MODULATING LAYOUT

CSE-1102

Air Differential Pressure Switch

VEP-45/

VEB-43

Valves

with

MEP-4002

0–10 VDC

Actuators

STE-1402

Duct Temp. Sensor, Type III

XEE-6311-050 Transformer

STE-1454

Strap-On Temp. Sensor, Type III

REE-3211 or CVR11C-0/LD96200 Multi-Voltage Relays

FCU (Fan Coil Unit)—2 Pipe, Modulating

Output

Terminals

FCU Output

Connections

BACnet

Objects

Analog 9

AO9

GND

Ground (for

analog output

terminals 7–9)

Analog 8

AO8

Analog 7

Valve (VLV)

AO7

Analog 6

AO6

GND
Analog 5

AO5

Analog 4

AO4

Relay 3

Fan 3

BO3

SC 1–3

24 VAC (for relay

terminals 1–3)

Relay 2

Fan 2

BO2

Relay 1

Fan 1

BO1

APPLICATION

DEGREES SCALE: °F

APP:

OPT: 2–PIPE
ADDITIONAL SETUP

FAN COIL

ADDITIONAL SETUP

FAN

OPTIMUM START
SENSORS
VALVE

NOTE: Do not use REE-3211/

CVR11C-0/LD96200

relay

s with analog

outputs! See Output

Connections on page 3.

Input Terminals

FCU Input Connections

BACnet Objects

IN9

Opt. Remote CO

2

Sensor*

AI9

IN8

AI8

IN7

Opt. Remote Temp. Sensor*

AI7

IN4

AI4

IN3

Supply Water Temp. (W-TMP)**

AI3

GND

Ground

IN2

Optional FST or DAT*

AI2

*Fan Status (FST), Discharge Air Temperature (DAT), and (not shown

on the diagram) remote temp./CO

2

sensors are optional inputs. Set

pull-up resistor switch positions appropriately (see the Input

Connections section).

**Input for Supply Water Temp is typically a 10K,Type III thermistor.