HTO-1103 FlexStat Firmware Flash Upgrade Kit

6

Installation Guide, Rev. N

5. When finished, close the software and unplug

power to the FlexStat.

CAUTION

Remove the power, then the USB cable, then the
pod, and then the backplate. Do not remove the
backplate with the pod still attached. Do not
remove either while power is still applied.

6. Remove the USB cable (before the pod).
7. Remove the pod.
8. Carefully remove the adapter plate

and reinstall

the WD jumper on the proper pins. (See

Illus-

tration 6 on page 4

.)

9. Carefully reinstall the FlexStat on the backplate

while being careful not to pinch or dislodge

any wiring.

10. Back the hex screws (counterclockwise) out of the

brackets until they engage the FlexStat cover and

hold it in place.

Troubleshooting

NOTE: See the cautions on pages 2 and 4!
• If a message appears that the operation has

failed, ensure the WD (watch dog) jumper is

TEMPORARILY removed during the upgrade

process! (See

Illustration 6 on page 4

.) Reinstall

the jumper after the upgrade process is com-

plete! After the update, a FlexStat with a missing

jumper may seem to be operating correctly, but it

may lock up at a later time.

NOTE: To replace a lost WD jumper, use a standard

2.54 mm computer jumper sourced locally. A

KMC HPO-0063 jumper can also be used if

the finger tab is cut off to clear the backplate.

• After the update process is over, if the FlexStat

display remains blank but the backlight is on

or the display locks up at a later time, check

that the WD jumper is reinstalled on the COR-

RECT pins. (See

Illustration 6 on page 4

.)

• If the USB port does not appear in the drop-

down list, close the tool, remove power to the

FlexStat, disconnect the FlexStat from the USB

port, reconnect the FlexStat to the USB port,

restore power to the FlexStat, and restart the tool.

• For any communication error (such as an “Oper-

ation has failed!” message) check all connections

and restart the Firmware Upgrade Tool. If the

HTO-1103 kit was received prior to Feb. 7, 2012

and has Rev. D on the silver label of the program-

ming pod, see the FlexStat Programming Pod

Jumper Position Service Bulletin SB0212A to

check for the correct jumper position within the

pod.

• For display/interface issues in the Firmware

Upgrade Tool, right-click in the firmware panel

(on the right) and select Restore Defaults.

• To view and download firmware updates from

within the tool or from KMC’s Partner Portal web

site (

partners.kmccontrols.com

), you must log-in

with a valid user name and password.

• Ensure firmware for the correct model is se-

lected in the Firmware Upgrade Tool. If firmware

for the wrong model is accidentally installed, the

outputs will not match the applications/configu-

ration on the display.

NOTE: Backing up the existing settings and

firmware image

before or during the

upgrade process (using the Firmware

Upgrade Tool, TotalControl, or BACstage)

is recommended practice.

NOTE: If custom Contol Basic programs are

installed, see

Custom Control Basic Issues

on page 8

.