S-5500 SSG and Captured Corner Mullion Installation Instructions

Section I: General Notes


F.

Follow EFCO framing installation and glazing instructions.


G.

Verify contents of all material shipments received upon their arrival. Verify

quantities and correct finishes. NOTIFY EFCO IMMEDIATELY OF ANY

DISCREPANCIES OR DAMAGE THAT MAY HAVE OCCURRED.

H.

Throughout these instructions the term “SEALANT” will appear. For the
purposes of these instructions, sealant is to be defined as the following:

SEALANT - A weather resistant, gunable liquid filler which when cured provides a
resilient, flexible (± 50% movement capability) air and water seal between

similar and dissimilar materials.
All sealant must meet ASTM C 920, CLASS 50.

BUTYL SEALANT- A non-skinning, non-hardening material (NAAMM
Reference Standard 5C-1).

NOTE: All sealant must be compatible with all surfaces on which adhesion is

required, including other sealant surfaces. All frame surfaces should be

clean, dry, dust, and frost free. If a primer is required, it must be
applied to clean surfaces. All perimeter substrates shall be clean and

properly treated to receive sealant.

This system is designed and has been tested to utilize butyl or silicone

sealants at all internal joineries, i.e., joint plugs, gasket intersections,
etc.

Regardless of the sealant used, the customer should contact the sealant

manufacturer to determine compatibility and adhesion. Follow sealant

manufacturer's proper application procedures and quality assurance
programs for weather sealing.


Maintain caulk joints as shown in the approved shop drawings. Unless

specified otherwise, most sealant manufacturers recommend a 3/8”
minimum perimeter caulk joint. A 3/4” minimum joint is recommended

at the head condition to accommodate thermal expansion and

contraction. A 3/4” minimum joint is required at the jamb conditions to
accommodate installation.

Anchoring surfaces of perimeter construction must be level and plumb

within the adjustable limits of the head, jamb, and sill framing.