; PRECAT BANK SETPOINT ****************************
; PreCat Oxygen Sensor Setpoint.
;
; Min Val Max Val
; 0.000 -> 0.840 (default) -> 1.000 (in Volts)
7151.2=0.840
; PRECAT BANK SETPOINT RATE ***********************
; PreCat Oxygen Sensor Setpoint Rate Limiting.
;
; Min Val Max Val
; 0.000 -> 10.000 (default) (in Volts/second)
7153.2=10.000
; PRECAT BANK PROPORTIONAL GAIN *******************
; Set Proportional Gain.
;
; Min Val Max Val
; 0.00 -> 2.00 (default) -> 10.00 (no units)
7172.2=2.00
; PRECAT BANK INTEGRAL GAIN ***********************
; Set Integral Gain Reset Time.
;
; Min Val Max Val
; 0.1 -> 10.0 (default) -> 60.0 (no units)
7175.2=10.0
; PRECAT BANK SLOW/FAST DYNAMICS ENABLE ***********
; 0 DISABLED (default)
; 1 ENABLED
7166.2=0
; PRECAT BANK SLOW/FAST DYNAMICS POSITIVE GAIN ****
; Set Positive Gain.
;
; Min Val Max Val
; 0.01 -> 1.00 (default) -> 10.00 (no units)
7162.2=1.00
; PRECAT BANK SLOW/FAST DYNAMICS NEGATIVE GAIN ****
; Set Negative Gain.
;
; Min Val Max Val
; 0.01 -> 1.00 (default) -> 10.00 (no units)
7163.2=1.00
; PRECAT BANK SLOW/FAST DYNAMICS SLOW THRESHOLD ***
; Set SLOW/LOW Threshold.
;
; Min Val Max Val
; 0.000 -> 1.000 (default) (in Volts)
7164.2=1.00