Dynalco AF-900PC Air/Fuel Ratio Controller User Manual
Page 61
60
; ***************** AI CHANNEL #05 ****************
; R MAP *******************************************
; AI CHANNEL ENABLE *******************************
; 0 DISABLED
; 1 ENABLED (default)
5500.5=1
; AI CHANNEL FILTER *******************************
; Averages new AI channel readings into
; current AI channel value by the following
; equation:
;
; Value = [Value_previous * (1 - filter)] + [Value_read * filter]
;
; Filter values near to 1.00 pass new
; readings very quickly. Filter values
; near to 0.00 pass new readings very
; slowly. A filter value of 0.00 does
; NOT pass new RPM readings at all.
;
; Slower filter values take longer to
; settle to the current RPM but have a
; high noise rejection and stability.
; Faster filter values settle quickly but
; have low noise rejection and stability.
;
; Min Val Max Val
; 0.00 -> 0.05 (default) -> 1.00 (no units)
5516.5=0.05
; AI CHANNEL MINIMUM UNITS ************************
;
; Min Val Max Val
; -10000.0 -> 0.0 (default) -> 10000.0 (in PSIG)
5532.5=0
; AI CHANNEL MAXIMUM UNITS ************************
;
; Min Val Max Val
; -50.0 -> 15.0 (default) -> 50.0 (in PSIG)
5533.5=15
;