; *************** TRIP CHANNEL #14 ****************
; PRECAT LEFT BANK VALVE HIGH LIMITED
; Fault on PreCat Valve stuck at maximum opening.

; TRIP MODE ***************************************
; Select TRIP Relay to activate on channel fault.
;
; 0 DISABLED (default)
; 1 ALARM RELAY
; 2 SHUTDOWN RELAY
; 3 AUX RELAY
600.14=0

; TRIP LOG ENABLE *********************************
; Trigger asynchronous LOG on channel fault.
;
; 0 DISABLED (default)
; 1 ENABLED
601.14=0

;/*$PAGE*/
; *************** TRIP CHANNEL #15 ****************
; PRECAT RIGHT BANK OXYGEN SENSOR FAULT ***********
; Fault on bad sensor OR sensor NOT detected.
; NOT applicable if sensor channel DISABLED.

; TRIP MODE ***************************************
; Select TRIP Relay to activate on channel fault.
;
; 0 DISABLED (default)
; 1 ALARM RELAY
; 2 SHUTDOWN RELAY
; 3 AUX RELAY
600.15=0

; TRIP LOG ENABLE *********************************
; Trigger asynchronous LOG on channel fault.
;
; 0 DISABLED (default)
; 1 ENABLED
601.15=0


; *************** TRIP CHANNEL #16 ****************
; PRECAT RIGHT BANK OXYGEN SENSOR HEALTH **********
; Fault on low sensor health.
; See OXYGEN SENSOR HEALTH section.

; TRIP MODE ***************************************
; Select TRIP Relay to activate on channel fault.
;
; 0 DISABLED (default)
; 1 ALARM RELAY
; 2 SHUTDOWN RELAY
; 3 AUX RELAY
600.16=0