ANALOG INPUTS CONFIGURATION SCREEN
This screen (Fig. 14) is used to set up the analog input system. It also shows the
current status of every channel.
NOTE: Specialized personnel should use this screen primarily to enable and
disable inputs for the application.
Analog Inputs Configuration Screen
Figure 14
Name: Name of each analog input channel. Channel names cannot be changed.
Type: Shows input type for each analog input channel. Type cannot be changed.
EU: Displays current measurement value for each analog input channel.
G-Cal: Factory gain calibration setting that should not be changed.
O-Cal: Factory offset calibration setting that should not be used.
Filter: Filter value applied to each input channel. The minimum value of 0.001
provides maximum filtering while the maximum value of 1.000 provides no filtering.
Fault: This column indicates each input channel’s fault status. All channels should
show “0” if there are no faults. Inputs faults are latching and must be cleared by
pressing the Reset button on the front panel.
En: This column is used to enable the required input channels. Entering EN
enables the channel, while entering DIS disables the channel. Enable the input
channels listed below: