; *************** TRIP CHANNEL #10 ****************
; PRECAT LEFT BANK EXHAUST TEMPERATURE LOW FAULT
; Fault on LOW PreCat Exhaust Temperature.
;
; Min Val Max Val
; 0 -> 575 (default) -> 2000 (in degrees F)
7211.1=575
; TRIP MODE ***************************************
; Select TRIP Relay to activate on channel fault.
;
; 0 DISABLED (default)
; 1 ALARM RELAY
; 2 SHUTDOWN RELAY
; 3 AUX RELAY
600.10=0
; TRIP LOG ENABLE *********************************
; Trigger asynchronous LOG on channel fault.
;
; 0 DISABLED (default)
; 1 ENABLED
601.10=0
; *************** TRIP CHANNEL #11 ****************
; PRECAT LEFT BANK EXHAUST TEMPERATURE HIGH FAULT
; Fault on HIGH PreCat Exhaust Temperature.
;
; Min Val Max Val
; 0 -> 2500 (default) (in degrees F)
7121.1=2500
; TRIP MODE ***************************************
; Select TRIP Relay to activate on channel fault.
;
; 0 DISABLED (default)
; 1 ALARM RELAY
; 2 SHUTDOWN RELAY
; 3 AUX RELAY
600.11=0
; TRIP LOG ENABLE *********************************
; Trigger asynchronous LOG on channel fault.
;
; 0 DISABLED (default)
; 1 ENABLED
601.11=0