beautypg.com

Dynalco AF-900PC Air/Fuel Ratio Controller User Manual

Page 77

background image

76

/*$PAGE*/
; *************** TRIP CHANNEL #23 ****************
; PRECAT TEMPERATURE SENSOR FAULT *****************
; Fault on bad sensor OR sensor NOT detected.
; NOT applicable if sensor channel DISABLED.

; TRIP MODE ***************************************
; Select TRIP Relay to activate on channel fault.
;
; 0 DISABLED (default)
; 1 ALARM RELAY
; 2 SHUTDOWN RELAY
; 3 AUX RELAY
600.23=0

; TRIP LOG ENABLE *********************************
; Trigger asynchronous LOG on channel fault.
;
; 0 DISABLED (default)
; 1 ENABLED
601.23=0




; *************** TRIP CHANNEL #24 ****************
; PRECAT TEMPERATURE LOW FAULT *******************
; Fault on LOW PreCat Temperature.
;
; Min Val Max Val
; 0 -> 1000 (default) -> 2000 (in degrees F)
7252=1000

; TRIP MODE ***************************************
; Select TRIP Relay to activate on channel fault.
;
; 0 DISABLED (default)
; 1 ALARM RELAY
; 2 SHUTDOWN RELAY
; 3 AUX RELAY
600.24=0

; TRIP LOG ENABLE *********************************
; Trigger asynchronous LOG on channel fault.
;
; 0 DISABLED (default)
; 1 ENABLED
601.24=0


; *************** TRIP CHANNEL #25 ****************
; PRECAT TEMPERATURE HIGH FAULT *******************
; Fault on HIGH PreCat Temperature.
;
; Min Val Max Val
; 0 -> 2500 (default) (in degrees F)
7253=2500