beautypg.com

Components/installation summary – Dynalco AF-900PC Air/Fuel Ratio Controller User Manual

Page 7

background image

6

5. Components/Installation Summary

5.1 System Components


Included

Single Bank Dual Bank

AF-900PC-3F

Air/Fuel

Ratio

Controller

(1)

(1)

400A-12959

Pre-Cat O2 Sensor Cable Ass’y (50 ft)

(1)

(2)

400A-12064

Post-Cat O2 Sensor Cable Ass’y (100 ft)

(1)

(1)

External Components (purchase separately)

Heated Pre-Cat Oxygen Sensor (Bosch p/n 15718)

(1)

(2)

Full-Authority

Fuel

Valve

(1)

(2)

Optional External Components (purchase separately)

M201

Magnetic Pickup for speed sensing

(1)

(1)

C101-XX

Pickup Cable for M201

(1)

(1)

Heated Post-Cat Oxygen Sensor (Bosch p/n 15718)

(1)

(1)

K

type

thermocouples

(ungrounded)

(2)

(2)

5.2 Installation Summary

1. Mount AF900PC Controller

2. Install Oxygen Sensor(s) in each engine exhaust bank

3. Run cables for Oxygen Sensors to controller (conduit must be used for Division 2

certification).

4. Install full-authority fuel valve(s)

5. Wire power to controller (10-30 VDC)

6. Install pickup for engine run signal and wire to controller. (Note: A contact closure run

signal may be used instead of the magnetic pickup).

7. Wire controller Alarm, Shutdown, and Auxiliary relay outputs to engine panel

shutdown and warning devices as required.