; *************** TRIP CHANNEL #12 ****************
; PRECAT LEFT BANK INTAKE TEMPERATURE HIGH FAULT
; Fault on HIGH PreCat Intake Manifold Temperature.
;
; Min Val Max Val
; 0 -> 2500 (default) (in degrees F)
7116.1=2500

; TRIP MODE ***************************************
; Select TRIP Relay to activate on channel fault.
;
; 0 DISABLED (default)
; 1 ALARM RELAY
; 2 SHUTDOWN RELAY
; 3 AUX RELAY
600.12=0

; TRIP LOG ENABLE *********************************
; Trigger asynchronous LOG on channel fault.
;
; 0 DISABLED (default)
; 1 ENABLED
601.12=0



;/*$PAGE*/
; *************** TRIP CHANNEL #13 ****************
; PRECAT LEFT BANK VALVE LOW LIMITED
; Fault on PreCat Valve stuck at minimum opening.

; TRIP MODE ***************************************
; Select TRIP Relay to activate on channel fault.
;
; 0 DISABLED (default)
; 1 ALARM RELAY
; 2 SHUTDOWN RELAY
; 3 AUX RELAY
600.13=0

; TRIP LOG ENABLE *********************************
; Trigger asynchronous LOG on channel fault.
;
; 0 DISABLED (default)
; 1 ENABLED
601.13=0