Dynalco AF-900PC Air/Fuel Ratio Controller User Manual
Page 85

84
/*$PAGE*/
; *************************************************
; *************** AIR/FUEL CONTROL ****************
; *************************************************
; AFC MODE ****************************************
; Select Air/Fuel Control Mode.
;
; 0 MANUAL
; 1 AUTO (default)
7000=0
; POSTCAT/PRECAT TEMPERATURE DIFFERENCE ENABLE ****
; 0 DISABLED
; 1 ENABLED (default)
7250=1
; POSTCAT/PRECAT TEMPERATURE DIFFERENCE FAULT DELAY
; Delay between PostCat/PreCat Temperature Delta
; Fault and fault action.
;
; Min Val Max Val
; 0 -> 10 (default) -> 240 (in minutes)
7258=10
; HEATER ENABLE ***********************************
; 0 DISABLED
; 1 ENABLED (default)
7300=1
; ******************** POSTCAT ********************
; POSTCAT ENABLE **********************************
; 0 DISABLED (default)
; 1 ENABLED
7010=1
; POSTCAT SETPOINT ********************************
; PostCat Oxygen Sensor Setpoint.
;
; Min Val Max Val
; 0.000 -> 0.702 (default) -> 1.000 (in Volts)
7031=0.702
; POSTCAT SETPOINT SELECT *************************
; Select PostCat Setpoint Source.
;
; 0 Requested Setpoint Request (default)
; 1 MAP Programming Setpoint (if MAP sensors ENABLED)
7033=0
;