Dynalco AF-900PC Air/Fuel Ratio Controller User Manual
Page 86
85
/*$PAGE*/
; *************** PRECAT LEFT BANK ***************
; PRECAT BANK ENABLE ******************************
; 1 ENABLED (default)
7100.1=1
; PRECAT BANK OXYGEN SENSOR FAULT ACTION **********
; Select Valve Output when Oxygen Sensor faults.
;
; 0 Output Fault Percent (default)
; 1 Output Opposite Bank Valve Percent
; 2 MAP Programming Table Percent (if MAP sensors ENABLED)
7113.1=0
; PRECAT VALVE MANUAL OUTPUT **********************
; Set Starting Valve Output.
; Output valid when Bank ENABLED and at Run RPM
; and in AFC MANUAL Mode.
;
; Min Val Max Val
; 0.0 (default) -> 100.0 (in valve opening %)
7184.1=0.0
; PRECAT VALVE START OUTPUT **********************
; Set Starting Valve Output.
; Output valid when Bank ENABLED and at Run RPM
; and in AFC AUTO Mode.
;
; Min Val Max Val
; 0.0 (default) -> 100.0 (in valve opening %)
7185.1=0.0
; PRECAT VALVE FAULT OUTPUT **********************
; Set Starting Valve Output.
; Output valid when Bank ENABLED and at Run RPM
; and in AFC AUTO Mode and Oxygen Sensor faulted
; and Sensor Fault Action set to Fault Percent.
;
; Min Val Max Val
; 0.0 (default) -> 100.0 (in valve opening %)
7186.1=0.0
;