Chapter 12

Configuring Hardware for the MicroVAX

Information Processors

12-10

If this device:

Then:

Displays this selfĆtest

error code:

DUALP

1

0000.0005 or 0000.0001

the device is okay.

<> 0000.0005 or

<>0000.0001

replace the module.

SCSIĆA

2

FFFFFF03

SCSI bus controller is connected to module and device is good.

00000001

disk drive is connected to module and device is good.

01000001

tape drive is connected to the module and device is good.

FFFFFF05

device is offline or not installed at this address. The SCSI ID may be

set incorrectly or the cabling may be disconnected. Check the cabling

and SCSI ID, then retest.

FFFFFFFF

device not tested - possible SCSI bus controller error

SCSIĆB

2

FFFFFF03

SCSI bus controller is connected to module and device is good.

00000001

disk drive is connected to module and device is good.

01000001

tape drive is connected to the module and device is good.

FFFFFF05

device is offline or not installed at this address.

FFFFFFFF

device not tested - possible SCSI bus controller error.

SYS

0000.0001

the device is good.

<> 0000.0001

replace the module.

BPI

2

0000.0001

the device is okay.

<>0000.0001

replace the module.

NI

0000.0001

the Ethernet port and cable are good.

>0000.0001 < 0000.7001

replace the module.

>= 0000.7001

install both TĆconnector terminators from the service kit and run the

test again. If you see 0000.0001, then replace the cable. If you do not

see 0000.0001, replace the module.

1

MicroVAX Information Processor (cat. no. 5730ĆCPU1) only.

2

MicroVAX Information Processor EP or EE (cat. nos. 5731ĆCPU1, ĆCPU2) only.

3.

Record the Ethernet address. It is on the second line of the system
configuration display table. For example:

ID 00-00-BC-01-01-C7

Run System Exerciser

You can use the system exerciser to:

test interaction between MicroVAX Information Processor devices
help determine the cause of intermittent problems
give more information about errors associated with the SCSI PORT

or LOADER