Chapter 11
Checking the Hardware
11-6
If you
have a:
If it is not:
It should be:
Check the LED
labeled:
1
MEM ERR will be on at initial power up until memory is cleared or downloaded.
2
These LEDs light after INTERCHANGE software has been loaded.
MicroVAX
Information
Processor
module
PASS/FAIL
GREEN
•
cycle power by turning off the power from the power supply and then
turning it back on.
•
make sure the module is seated properly Ċ see appendix A.
ENET CH A
Flashing GREEN (If
connected and
communicating on the
Ethernet network)
make sure the connection to the Ethernet network is secure.
PROCESSOR
OFF
2
BACKPLANE
OFF
2
ENET CH B
OFF
ERROR
OFF
•
cycle power by turning off the power from the power supply and then
turning it back on.
•
make sure the module is seated properly Ċ see appendix A.
•
it will blink the error code. Call support services.
BATTERY LOW
OFF
make sure the battery is inserted correctly in the battery holder.
KA module PASS/FAIL
GREEN
•
make sure you turn on the power to the power supply.
•
cycle power by turning off the power from the power supply and then
turn it back on.
MEM ERR
1
OFF
make sure the memory module is connected properly Ċ see appendix A.
CH 1
Flashing GREEN
(if connected)
make sure the connection is secure.
CH 2
Flashing GREEN (if
configured as DH+ link)
CH 3
Flashing GREEN (if
configured as DH+ link)
OSI
Interface
Module
PASS/FAIL
GREEN
•
cycle power by turning off the power from the power supply and then
turning it back on.
•
make sure you turn on the power to the power supply.
•
make sure the module is seated properly Ċ see appendix A.
•
if cycling power doesn't work, replace the OSI Interface module.
MODE
GREEN
download the program image using AĆB MAP Station Manager.
ACTIVITY
Flashing GREEN (If MAP interface is passing a message.)
MEM ERR
OFF
•
cycle power by turning off the power from the power supply and then
turning it back on.
•
make sure you turn on the power to the power supply.
•
if cycling power doesn't work, replace the OSI Interface module.
BATT LOW
OFF
•
make sure the battery is inserted correctly in the battery holder.
•
the lithium battery is weak and should be replaced.
COMM STATUS
GREEN
•
if the LED is OFF, check 802.4 cable connections. Or check slot time.
•
if the LED is flashing RED, reset the module through the RSĆ232 local
interface or through a power cycle.
•
if the LED is RED, reset the module through the RSĆ232 local
interface or through a power cycle.
•
if resetting the module doesn't work, contact your local AĆB sales
office.