Checking module indicator lights, Connecting the program loader, Setting up the terminal – Rockwell Automation 5000,D50006.2.10 PI INSTALLATION MANUAL User Manual
Page 140

Chapter 12
Configuring Hardware for the MicroVAX
Information Processors
12-2
Checking Module Indicator Lights
Use the following table to check the module indicator lights.
Check the LED labeled:
1
It should be:
If it is not:
PASS/FAIL
GREEN
•
cycle power by turning off the power from the power supply
and then turning it back on.
•
make sure the module is seated properly, see appendix A.
ENET A
2
or ENET
Flashing GREEN
(If connected and
communicating on
Ethernet)
make sure the Ethernet connection is secure.
PROCESSOR
OFF
1
BACKPLANE
OFF
1
ERROR
OFF
•
cycle power by turning off the power from the power supply
and then turn it back on.
•
make sure the module is seated properly Ċ see
appendix A.
•
note the blinking error code; count the flashes between
pauses and be prepared to give that information to
support services.
BATTERY LOW
OFF
Make sure the battery is inserted correctly in the battery holder.
1
These LEDs light after Interchange software has been loaded.
2
ENET A is for the MicroVAX Information Processor and ENET is for the MicroVAX Information Processor EP or EE.
Connecting the Program Loader
If you are using the program loader (series A or B), you should have
already connected it to the module. Make sure you have rebooted the
system at least once since the program loader was connected, or the
MicroVAX Information Processor will not recognize that the program
loader is connected. See the Program Loader Installation Data
(5000-2.93) for more information.
Setting Up the Terminal
To set up the console terminal, complete the following steps:
1.
Attach the terminal to port 3 (OPA0) on the distribution panel.
2.
Set the terminal to:
9600 baud
transmit = receive
8 bits
no parity
1 stop bit
no local echo