Chapter 9

Connecting the I/O Link

9-2

For RS, always ground one and only one end of the shield.

Figure 9.1

General Cabling Configuration

End

device

End

device

Middle

device(s)

Blue

Shield

Clear

Blue

Shield

Clear

Blue

Shield

Clear

Blue

Shield

Clear

Twinaxial cable (cat. no. 1770ĆCD)

See the table in previous section for the maximum length.

150

or

82

150

or

82

16507

Connecting Remote I/O to the RS

Follow the steps below to connect your remote I/O link cable to the RS.

1.

Locate the I/O channel connection on the I/O wiring information.

2.

Wire the I/O channel as shown in the wiring documentation.

Blue 1

Shield

Clear 2

RS5

19789

a. Remove the male connectors for ports labeled

CH 1, CH 2, CH3

1

and CH4

1

.

b. Wire these connectors using Twinaxial Cable

(cat. no. 1770ĆCD).

c. According to the I/O documentation from your

system designer, attach wired connectors to the

appropriate female connectors.

d. Connect the other end of the cable to the

remote I/O adapter module or processor module

in the remote system.

e. If there ia a 1771ĆAS, ĆASB module at the end

of the remote I/O link, connect a terminator (cat.

no. 1770ĆXT) between the terminals on the

adapter module.

1

This applies to RS5 only.