Connecting to a direct communication module, Connecting to a redipanel module – Rockwell Automation 5000,D50006.2.10 PI INSTALLATION MANUAL User Manual
Page 121
Chapter 9
Connecting the I/O Link
9-8
Figure 9.7 shows I/O link connections to a direct communication module
(1771-DCM) both as a middle device and as an end device on a link. The
clear-insulation conductor connects to the top terminal. The
blue-insulation conductor connects to the bottom terminal. At each direct
communication module, connect the shield drain wire of each cable
segment to give the shield continuity. However, never ground the shield at
a direct communication module. At a direct communication module
connected as an end device on a link, connect a 150-Ohm 1/4-Watt
termination resistor across the signal lines.
Figure 9.7
Connections to Direct Communication Module
Blue
Shield
Clear
To
scanner
Blue
Shield
Clear
Blue
Shield
Clear
Direct communication module Direct communication module
150
Ω
16514
ATTENTION: Do not disconnect the connector on a middle
device when the system is operating because that would cause
discontinuity in the link and remove the termination.
The connection between terminals is inside the module.
shows I/O link connections to a 2705 RediPANEL module both
as a middle device and as an end device on a link. The blue-insulation
conductor connects to the top terminal. The clear-insulation conductor
connects to the bottom terminal. At each RediPANEL module, connect the
shield drain wire of each cable segment to give the shield continuity.
However, never ground the shield at a RediPANEL module. At a
RediPANEL module connected as an end device on a link, connect a
150-Ohm 1/4-Watt termination resistor across the signal lines.
Connecting to a Direct
Communication Module
Connecting to a RediPANEL
Module