Connect the Kinetix 7000 Drive System
Chapter 4
Grounding the Kinetix 7000
Drive System
All equipment and components of a machine or process system must have a
common earth ground point connected to their chassis.
A grounded system provides a ground path for short-circuit protection.
Grounding your modules and panels minimize shock hazard to personnel and
damage to equipment caused by short-circuits, transient overvoltages, and
accidental connection of energized conductors to the equipment chassis.
See Agency Compliance on page
for CE grounding requirements.
Grounding Your System to the Subpanel
, the drive is shown properly grounded to the bonded cabinet ground
on the subpanel.
Figure 50 - Drive Chassis Ground Connection
IMPORTANT
To improve the bond between the drive and subpanel, construct your
subpanel out of zinc-plated (paint-free) steel.
ATTENTION: The National Electrical Code contains grounding requirements,
conventions, and definitions. Follow all applicable local codes and regulations
to safely ground your system.
See the Interconnect Diagram Notes diagrams beginning on page
.
Ground grid or power
distribution ground *
Bonded Cabinet Ground *
Braided Ground Strap *
* Indicates customer-supplied item.
Kinetix 7000
Drive