Contactor ratings, Power dissipation specifications – Rockwell Automation 2099-BMxx Kinetix 7000 High Power Servo Drive User Manual User Manual
Page 152

152
Rockwell Automation Publication 2099-UM001D-EN-P - December 2012
Appendix A
Specifications and Dimensions
Table 60 - Bussmann Fuse Recommendations
Contactor Ratings
The table below lists the recommended contactor ratings for Kinetix 7000 drives
installed without a Line Interface Module (LIM).
Power Dissipation
Specifications
Use this table to size an enclosure and calculate required ventilation for your
Kinetix 7000 drive system.
Drive Cat. No.
Drive Current
Rating (Adc)
Recommended
Fuse
Fuse Current
Rating
i²t (A²Sec)
Peak Let-Through Current
at 100kA rms
Pre-Arc
Max Clearing @
600V AC
2099-BM06-S
42.9
FWJ-80A
80
1550
9700
6300 A
2099-BM07-S
55.7
FWJ-100A
100
2800
17500
8000 A
2099-BM08-S
69.7
FWJ-125A
125
4800
35000
10000 A
2099-BM09-S
105
FWJ-175A
175
7500
65000
12000 A
2099-BM10-S
137
FWJ-200A
200
11700
80000
13000 A
2099-BM11-S
204
FWJ-500A
500
39500
329000
21000 A
2099-BM12-S
281
FWJ-500A
500
39500
329000
21000 A
Drive Cat. No.
Contactor
Safety Contactor
Coil Type
Coil Voltage Requirements
2099-BM06-S
100-C43DJ01
100S-C43-DJD4C
Standard with Diode
24V DC
2099-BM07-S
100-D95EN11
100S-D95EN22C
Electronic Coil
(1)
24V DC for control and 480V AC for coil power
2099-BM08-S
2099-BM09-S
2099-BM10-S
100-D140EN11
100S-D140EN22C
2099-BM11-S
100-D180EN11
100S-D180EN22C
2099-BM12-S
100-D250EN11
100S-D250EN22C
(1) Electronic coil control power requirements = 24V DC @ 15 mA.
Drive Cat. No.
Usage as a % of Rated Power Output
W
50%
100%
2099-BM06-S
294
465
2099-BM07-S
388
619
2099-BM08-S
452
730
2099-BM09-S
645
1072
2099-BM10-S
882
1479
2099-BM11-S
1275
2125
2099-BM12-S
1438
2437