Module Configuration, Output, and Input Data
Chapter 4
ToThisCtr - Range Counter Number (Range12To15[
n
].ToThisCounter)
This 2-bit value indicates which counter will be used in the range comparison or
Range12To15[
n].LoadDirectWrite. The counter is indicated in the table below.
If Range12To15[
n].ToThisCounter is set to a number larger than
NumberOfCounters in the configuration array, then the
InvalidCtrAssignToRange
n error bit in the input array will be set.
Type - RangeType (Range12To15[
n
].Type)
This bit value indicates which type of value to use for the range comparison in
Range. That is, the Range12To15[
n].ToThisCounter, from above, and this
Range12To15[
n].Type value determine the rate or count value, the current value
which is compared to, for the range comparison. The type of value is indicated as
follows:
• 0 = Count Value
• 1 = Rate Value
When Range12To15[
n].LoadDirectWrite is set Range12To15[n]. Type is
ignored.
LDW - Load Direct Write (Range12To15[
n
].LoadDirectWrite)
A 0 to 1 transition of this bit causes counter (
n)’s current count value to change to
the value of Range12To15[
n].HiLimOrDirWr.
Bit 01
Bit 00
Counter
0
0
0
0
1
1
1
0
2
1
1
3
IMPORTANT
For the L23E packaged controllers embedded HSC, the range type is fixed
at 0, which sets the range type to count value. The ranges in this section
apply to only the 1769-HSC module and the CMX 5370 L2 packaged
controllers embedded HSC.
IMPORTANT
The write occurs according to the internal timings of the module and the
system. For the most predictable results, the counter should be disabled
or stopped while performing this action.
IMPORTANT
If both CtrnSoftPreset and Range12To15[n].HiLimOrDirWr transition to 1
during the same Output Array update, only the CtrnSoftPreset occurs.
Range12To15[n].HiLimOrDirWr is ignored.