D - programming quick reference, Appendix d, Programming quick reference – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual
Page 149: Appendix

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013
149
Appendix
D
Programming Quick Reference
This appendix section for the 1769-HSC Module contains at-a-glance lists of the
following:
• Configuration array
• Output array
• Input array
The default value for the configuration array is all zeros, except where noted.
IMPORTANT
The information in this appendix does not apply to the packaged
controllers.
Table 30 - Configuration Array for the 1769-HSC Module
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Description
0
Individual Counter Reset Disable
(1)
NumberOfCtrs
PFE
CtrRst
OCLO
GeneralConfigBits
®
OvercurrentLatchOff
CtrReset
ProgToFaultEn
NumberOfCounters_0
(2)
NumberOfCounters_1
1
Filter_Z1
Filter_B1
Filter_A1
Filter_Z0
Filter_B0
Filter_A0
FilterA0_0, FilterA0_1 -- ...Z1_1
2
Out3
PSR
Out2
PSR
Out1
PSR
Out0
PSR
Out3
PM
Out2
PM
Out1
PM
Out0
PM
Out0ProgramStateRun --Out3... and
Out0ProgramMode -- Out3...
3
Out3
PV
Out2
PV
Out1
PV
Out0
PV
Out0ProgramValue --- Out3...
4
Out3
FSR
Out2
FSR
Out1
FSR
Out0
FSR
Out3
FM
Out2
FM
Out1
FM
Out0
FM
Out0FaultStateRun --Out3FaultStateRun and
Out0FaultMode -- Out3FaultMode
5
Out3
FV
Out2
FV
Out1
FV
Out0
FV
Out0FaultValue -- Out3FaultValue
6
7
Ctr0MaxCount
(3)
Ctr0MaxCount
8
9
Ctr0MinCount
(4)
Ctr0MinCount
10
11
Ctr0Preset
Ctr0Preset
12
Ctr0Hysteresis
Ctr0Hysteresis
13
Ctr0Scalar
(5)
Ctr0Scalar
14
Ctr0CyclicRateUpdateTime
(6)
Ctr0CyclicRateUpdateTime
15
Linear
Storage Mode
Operational Mode
Ctr0ConfigFlags
®
Ctr0Config.OperationalMode_0
Ctr0Config.OperationalMode_1
Ctr0Config.OperationalMode_2
Ctr0Config.StorageMode_0
Ctr0Config.StorageMode_1
Ctr0Config.StorageMode_2
Ctr0Config.Linear
16
17
Ctr1MaxCount
(3)
Ctr1MaxCount
18
19
Ctr1MinCount
(4)
Ctr1MinCount
20
21
Ctr1Preset
Ctr1Preset
22
Ctr1Hysteresis
Ctr1Hysteresis
23
Ctr1Scalar
(5)
Ctr1Scalar
24
Ctr1CyclicRateUpdateTime
(6)
Ctr1CyclicRateUpdateTime
25
Linear
Storage Mode
Operational Mode
Ctr1ConfigFlags
®
Ctr1Config.OperationalMode_0
Ctr1Config.OperationalMode_1
Ctr1Config.OperationalMode_2
Ctr1Config.StorageMode_0
Ctr1Config.StorageMode_1
Ctr1Config.StorageMode_2
Ctr1Config.Linear
26
27
Ctr2MaxCount
(3)
Ctr2MaxCount
28
29
Ctr2MinCount
(4)
Ctr2MinCount
30
31
Ctr2Preset
Ctr2Preset
32
Ctr2Hysteresis
Ctr2Hysteresis
33
Ctr2Scalar
(5)
Ctr2Scalar
34
Ctr2CyclicRateUpdateTime
(6)
Ctr2CyclicRateUpdateTime
35
Linear
Ctr2ConfigFlags
®
Ctr2Config.Linear
36
37
Ctr3MaxCount
(3)