Range configuration flags (12to15) – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual
Page 96
96
Rockwell Automation Publication 1769-UM006E-EN-P - July 2013
Chapter 4
Module Configuration, Output, and Input Data
Range Output Control (Range12To15[n].OutputControl)
This 16-bit word indicates which outputs should be on (corresponding bit set in
this word) when a range is active. When Range
n is enabled and active,
Range12To15[
n].OutputControl will be logically OR’ed with other
Range12To15[
n].OutputControl masks and the OutputOnMask.n and so forth.,
as described on
.
When Range12To15[
n].LoadDirectWrite is set,
Range12To15[
n].OutputControl is ignored.
Range Configuration Flags (12To15)
IMPORTANT
For the L23E packaged controllers embedded HSC, the ranges referred to
in this section are numbered 0…3 instead of 12…15. The ranges in this
section apply to only the 1769-HSC module and the CMX 5370 L2
packaged controllers embedded HSC.
Output Array Words
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
14
Range 12 Output Control
Range12To15[0].OutputControl
20
Range 13 Output Control
Range12To15[1].OutputControl
26
Range 14 Output Control
Range12To15[2].OutputControl
32
Range 15 Output Control
Range12To15[3].OutputControl
IMPORTANT
For the L23E packaged controllers embedded HSC, the ranges referred to
in this section are numbered 0…3 instead of 12…15. The ranges in this
section apply to only the 1769-HSC module and the CMX 5370 L2
packaged controllers embedded HSC.
Output Array Words
15
14
13
12
11
10
09
08
07
06
05
04
(1)
03
02
01
00
15
Range 12 Configuration Flags
Not used
Inv
Not used
LDW
Type
Not used
ToThisCtr
21
Range 13 Configuration Flags
Not used
Inv
Not used
LDW
Type
Not used
ToThisCtr
27
Range 14 Configuration Flags
Not used
Inv
Not used
LDW
Type
Not used
ToThisCtr
33
Range 15 Configuration Flags
Not used
Inv
Not used
LDW
Type
Not used
ToThisCtr
(1) Bit 04 is not used for the packaged controller.