OCLO - Overcurrent Latch Off (OverCurrentLatchOff)
When set, this bit causes the module to make any overcurrent activity latch the
corresponding output off, simulating a physical fuse. When OCLO = 0, it
automatically resets. The rising edge of RBF resets the output.
36
Ctr3MaxCount
Counter 3 Maximum
Count
37
38
Ctr3MinCount
Counter 3 Minimum
Count
39
40
Ctr3Preset
Counter 3 Preset
41
42
Not used
Not used
43
Not used
Not used
44
Not used
Not used
45
Not used
Lin-
ear
Not used
Counter 3
Configuration Flags
Table 13 - Configuration Array - L23E Packaged Controller Embedded HSC (Continued)
Word
Bit
Function
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Configuration Array Word 0
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
General Configuration Bits
Individual Counter
Reset Disable
(1)
Number of counters
Not used
PFE
Not used
Ctr
Reset
OCL
O
(1) For the 1769-HSC/B module only. Bit 12 is Counter 0 reset disable; Bit 13, Counter 1 reset disable; Bit 14, Counter 2 reset disable; Bit 15, Counter 3 reset disable.
Counter reset function = 0: reset enable (default), 1: reset disable. The 1769-HSC/A module does not use bits 12…15 in the configuration array. See
page 73
for details.
IMPORTANT
Do not set this bit while a counter or range is enabled (Ctr0En, Ctr1En,
Ctr2En, Ctr3En, or RangeEn set to 1). Attempting to do so will result in a
BadModConfigUpdate error.
See
for a list of prohibited settings.