Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual
Page 120

120
Rockwell Automation Publication 1769-UM006E-EN-P - July 2013
Chapter 5 Diagnostics and Troubleshooting
The BadModConfigUpdate error conditions are shown in the following table.
They occur when you attempt to change a forbidden module configuration
parameter while a counter or range is still enabled. To recover from this situation,
do the following:
• Correct the configuration problem.
• Reconfigure the module.
TIP
Refer to your controller’s documentation for available reconfiguration
methods.
IMPORTANT
Do not change the module settings in
while counter or range is
enabled.
Table 24 - ‘BadModConfigUpdate’ Error Prohibited Configuration Settings
Configuration Parameters
Array Position
Prohibited from changing when indicated bits (X) are set
Word
Bit
Ctr0EN
Ctr1EN
Ctr2EN
Ctr3EN
RangeEN
OverCurrentLatchOff
0
0
X
X
X
X
X
ProgToFaultEn
0
4
NumberOfCounters
0
8 and 9
X
X
X
X
X
Filter_A0
1
0 and 1
X
X
Filter_B0
1
3 and 4
X
X
Filter_Z0
1
6 and 7
X
X
Filter_A1
1
8 and 9
X
X
Filter_B1
1
11 and 12
X
X
Filter_Z1
1
14 and 15
X
X
OutnProgramMode
2
0 to 3
OutnProgramStateRun
2
4 to 7
OutnProgramValue
3
0 to 3
Outn0FaultMode
4
0 to 3
OutnFaultStateRun
4
4 to 7
OutnFaultValue
5
0 to 3
Ctr0MaxCount
Ctr0MinCount
Ctr0Preset
(1)
Ctr0Hysteresis
(2)
Ctr0Scalar
Ctr0CyclicRateUpdateTime
Ctyr0Config.OperationMode
Ctr0Config.StorageMode
Ctr0Config.Linear
6 and 7
8 and 9
10 and 11
12
13
14
15
15
15
--
--
--
--
--
--
0 to 3
8 to 10
12
X
X
X
X
X
X
X
X