Overcurrent, Safe state control, Overcurrent safe state control – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual
Page 40

40
Rockwell Automation Publication 1769-UM006E-EN-P - July 2013
Chapter 2
Module Operation
Overcurrent
If the module detects a real output point overcurrent condition, it reports it to
the input file and turns off that output. You can also program the module to
latch each of the four real outputs off, emulating a physical fuse, or to
automatically reset. The 12 virtual outputs do not have this function.
When the OvercurrentLatchOff bit is set and an overcurrent situation occurs,
even momentarily, the associated real output is latched off until the
ResetBlownFuse bit transitions from 0 to 1.
If the OvercurrentLatchOff bit is reset and an overcurrent situation occurs, the
output turns off for 1 second and is then retried (auto-reset). The module
continues to attempt to turn the output back on until the overcurrent situation is
no longer detected and the output is successfully turned back on.
Safe State Control
The 1769-HSC module combines the Hold Last State and User-defined Safe
State options with a safe-state run alternative that lets the module to continue to
control outputs under program or fault states
(1)
. These Safe State options are not
available in the packaged controllers.
Only the physical outputs are affected by safe state settings and conditions.
Virtual outputs, inputs, and counting are not affected by program or fault states.
Hold Last State (HLS)
This condition applies depending on the mode of the controller. When the hold
last state option is set, the module holds the outputs at the state they were at just
before the control system transitioned from Run to Program or Run to Fault.
HLS sets the module according to the values configured for Program mode
(described on
) and Output Fault mode (described on
User-defined Safe State (UDSS)
In this configuration, the module sets the outputs to a user-defined safe state
when the control system transitions from Run to Program or Run to Fault.
UDSS sets the module according to the values configured for Output Program
Value (described on
) and Output Fault Value (described on
IMPORTANT
The outputs will be on momentarily while they are retried. The length of
time they are on depends on the magnitude of the load.
(1) The module continues to update the input array and count inputs in all modes. The operation of the outputs will
vary according to mode, configuration, and the capabilities of the controller or bus master.