Cyclic Rate Update Time (CtrnCyclicRateUpdateTime)
This value is used to set the cyclic rate update time for the CurrentRate
calculation. The value indicates the time in milliseconds from 1…32767. An
invalid number causes a configuration error. The default value is 10 for counters 0
and 1. The default value is 0 for counters 2 and 3.
See
Cyclic Rate Calculation Method (current rate) on page 32
for more
information on cyclic rate.
IMPORTANT
Do not change this value while the counter is enabled. Attempting to do
so will result in a BadModConfigUpdate error. See
for a list
of prohibited settings.
IMPORTANT
The Counter Scalar information does not apply to the L23E packaged
controller because rate measurement is not supported.
Configuration Array Words
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
14
Counter 0 Cyclic Rate Update Time
Ctr0CyclicRateUpdateTime
24
Counter 1 Cyclic Rate Update Time
Ctr1CyclicRateUpdateTime
34
Counter 2 Cyclic Rate Update Time
Ctr2CyclicRateUpdateTime
44
Counter 3 Cyclic Rate Update Time
Ctr3CyclicRateUpdateTime
IMPORTANT
Do not change this value while the counter is enabled. Attempting to do
so will result in a BadModConfigUpdate error. See
for a list of
prohibited settings.