Din rail mounting – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual
Page 52
![background image](/manuals/579645/52/background.png)
52
Rockwell Automation Publication 1769-UM006E-EN-P - July 2013
Chapter 3
Installation and Wiring
Panel Mounting Procedure By Using Modules as a Template
This procedure lets you use the assembled modules as a template for drilling holes
in the panel. Due to module mounting hole tolerance, it is important to follow
these procedures:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all
module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any
previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel, and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.
7. Repeat steps
1
through
6
for any remaining modules.
DIN Rail Mounting
The module can be mounted on the following DIN rails:
• EN 50 022 - 35 x 7.5 mm (1.38 x 0.3 in.)
• EN 50 - 35 x 15 mm (1.38 x 0.59 in.)
1. Before mounting the module on a DIN rail, close the DIN rail latches.
2. Press the DIN rail mounting area of the module against the DIN rail.
The latches will momentarily open and lock into place.
Figure 13 - DIN Rail Mounting Dimensions
TIP
If mounting more modules, mount only the last one of this group
and put the others aside. This reduces remounting time during
drilling and tapping of the next group.
A
B
C
Dimension
Height
A
118 mm (4.65 in.)
B
59 mm (2.325 in.)
C
59 mm (2.325 in.)