Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

75

Module Configuration, Output, and Input Data

Chapter 4

PFE - Program to Fault Enable (ProgToFaultEn)

This bit indicates what should happen when the bus controller indicates a change
from one condition (Program mode) to another (Fault mode). If this bit is set (1),
the safe state operation of all four real outputs changes to that identified by the
Fault State and Fault Value words. If this bit is reset (0), the module continues
with the operation identified by the Program State and Program Value words.

Number of Counters (NumberOfCounters)

This 2-bit value indicates whether the module uses 1 counter, 2 counters,
3 counters, or 4 counters. The default value is 1 (2 counters).

Filter Selection

This value indicates the nominal filter frequency as shown in the table.

Bit 01

Bit 00

Counters

0

0

1

0

1

2

1

0

3

1

1

4

IMPORTANT

Do not set this value while a counter or range is enabled (Ctr0En, Ctr1En,
Ctr2En, Ctr3En, or RangeEn set to 1). Attempting to do so will result in a
BadModConfigUpdate error.

See

page 120

for a list of prohibited settings.

Configuration Array Word 1

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Filter Selection

Filter_Z1

Not
used

FilterB1

Not
used

FilterA1

FilterZ0

Not
used

FilterB0

Not
used

FilterA0

Filters and
Corresponding Bits

FilterA0

Bit 1 - FilterA0_1

Bit 0 - FilterA0_0

FilterB0

Bit 4 - FilterB0_1

Bit 3 - FilterB0_0

FilterZ0

Bit 7 - FilterZ0_1

Bit 6 - FilterZ0_0

FilterA1

Bit 9 - FilterA1_1

Bit 8 - FilterA1_0

FilterB1

Bit 12 - FilterB1_1

Bit 11 - FilterB1_0

FilterZ1

Bit 15 - FilterZ1_1

Bit 14 - FilterZ1_0

Nominal
Frequency
Settings

None

0

0

0.01 ms minimum pulse width
(0.0185 ms for the packaged controller)

0

1

0.5 ms minimum pulse width
(0.715 ms for the packaged controller)

1

0

5 ms minimum pulse width
(7.1 ms for the packaged controller)

1

1