Setting up the module, Chapter 5, Chapter – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual
Page 73

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
73
Chapter
5
Configure the Module in a GuardLogix Controller
System
Setting Up the Module
When using a GuardLogix controller on an EtherNet/IP network, configure the
POINT
Guard I/O
modules by using the Logix Designer application.
At the bottom of each dialog box, click Help for information about how to
complete entries in that dialog box. At the bottom of warning dialog boxes, click
Help for information about that specific error.
When first setting up your POINT Guard I/O modules on an EtherNet/IP
network, perform the following steps.
1.
Add and Configure the Ethernet Bridge Module
.
2.
Add and Configure the 1734 Ethernet Adapter
.
3.
Add and Configure Safety Digital Input Modules
.
4.
Add and Configure Safety Digital Output Modules
.
5. Add and Configure Safety Analog Input Modules
Topic
Page
Add and Configure the Ethernet Bridge Module
Add and Configure the 1734 Ethernet Adapter
Add and Configure Safety Digital Input Modules
Add and Configure Safety Digital Output Modules
Add and Configure Safety Analog Input Modules
Saving and Downloading the Module Configuration
IMPORTANT
You must configure each point that is to be used as a safety input or output.
By default, all safety input and output points are disabled.
TIP
If you need an add-on profile, visit the My Support website a